Ice on the evaporator means defrost
A light frost is normal. A solid block that closes the fin gaps is not. It usually means the defrost heaters, the termination sensor or the control settings are not completing a full cycle, so each frost is added to rather than cleared.
The symptom people notice first is reduced pull-down: the room runs constantly and still struggles after a delivery. By then airflow has often been restricted for weeks.
Ice on the floor means the drain
Water that should leave through the drain is freezing on the floor instead. The common causes are a blocked drain, a failed drain heater or trace, or a fall that was never correct. Once the drain freezes, the room starts holding water as well as cold.
This is the one to fix immediately. Melt water finds floor finishes, stock packaging and door gear, and the repair grows with every week it is left.
Ice on the frame or around the door
Ice around a door frame points at the envelope rather than the plant: a hardened gasket, a closer that no longer latches, a damaged heated frame or a threshold that has been damaged by trolleys.
Every opening admits moist air that the evaporator must turn into ice. A door that seals properly reduces the load on the plant more than a larger unit would.